Wire Size Formula:
From: | To: |
Definition: This calculator determines the appropriate wire size (cross-sectional area) needed for a 22kW generator installation based on current, distance, and acceptable voltage drop.
Purpose: Ensures safe and efficient power transfer from generator to load while maintaining voltage within acceptable limits.
The calculator uses the formula:
Where:
Explanation: The formula calculates the minimum wire size needed to keep voltage drop within specified limits for a given current over a specific distance.
Details: Correct wire sizing prevents excessive voltage drop (which can damage equipment), reduces heat generation, and ensures efficient power transfer.
Tips:
Q1: Why is voltage drop important for generators?
A: Excessive voltage drop can cause equipment malfunction, reduce efficiency, and potentially damage sensitive electronics.
Q2: What's the typical current for a 22kW generator?
A: At 240V, approximately 91.7A (22,000W ÷ 240V = 91.7A).
Q3: When would I use aluminum instead of copper?
A: Aluminum (K=21.2, σ=36) may be used for long runs or cost savings, but requires larger wire sizes.
Q4: How do I convert mm² to AWG?
A: Use a wire gauge chart. For example: 16mm² ≈ 6 AWG, 25mm² ≈ 4 AWG, 35mm² ≈ 2 AWG.
Q5: Does this account for temperature or conduit fill?
A: No, consult NEC tables for additional derating factors based on installation conditions.